Grounding and bonding

Bonding Jumper Sizing Reference

Look up a main, system, or supply-side bonding jumper from ungrounded conductor size, material, and parallel raceway arrangement.

Grounding and bonding inputs

Bonding jumper details

sets

Use one set for this arrangement.

Minimum bonding jumper

Minimum bonding jumper size

4 AWGCu
Table band2/0 or 3/0 AWG copper
Equivalent phase area167.8 kcmil
Bonding jumpers1
Sizing basisTable 270.102(C)(1) lookup
Reference onlyThis screen applies the supply-side/main/system bonding-jumper table basis. It does not size load-side equipment bonding jumpers, grounding electrode conductors, grounded conductors, or every parallel-installation exception. Confirm the adopted NEC edition, equipment instructions, and local requirements.

About this reference

Use the inputs to look up a minimum conductor size for a main bonding jumper, system bonding jumper, or supply-side bonding jumper. The result is based on the largest ungrounded conductor or the equivalent area of parallel conductors.

Method and assumptions

For separate parallel raceways, the individual-per-raceway option sizes each jumper from the conductor set in that raceway. The common-jumper option sums the largest ungrounded conductor areas from all parallel sets before selecting one jumper. A single conductor set uses the selected conductor size directly.

When the equivalent area exceeds the listed copper or aluminum range, the calculator applies the 12.5% area note and rounds up to a listed conductor size. This screen does not make the installation compliant by itself.

FAQs

What does this reference size?

It applies the alternating-current table basis for a main bonding jumper, system bonding jumper, or supply-side bonding jumper. The load-side equipment bonding jumper uses a different equipment grounding conductor basis.

How should I handle parallel raceways?

Select an individual jumper in each raceway when each raceway is bonded separately. Select one common jumper when a single jumper bonds the parallel raceways and the table basis uses the sum of the largest ungrounded conductors from the parallel sets.

What happens above the table range?

The calculator applies the 12.5% area note to the largest conductor or equivalent parallel area, then rounds up to the next listed conductor size. Material-equivalency requirements and installation-specific rules still need a separate review.