Industrial enclosure thermal planning

Enclosure Cooling Capacity Calculator

Estimate enclosure cooling demand from internal losses, enclosure dimensions, ambient conditions, and an entered effective heat-transfer coefficient.

Enclosure cooling estimate

Enter heat load and enclosure assumptions

W
W
in
in
in
°F
°F
W/m²·K

Enter a supported effective value for the enclosure construction; this varies with material, insulation, mounting, and airflow.

Steady-state heat balance

Estimated active cooling capacity

1,314.2 BTU/h
Required cooling385.2 W
Enclosure surface area2.04 m²
Passive ambient heat transfer85.2 W
Estimate onlyAssumes a six-sided enclosure and a user-supplied effective heat-transfer coefficient. This is not a cooling unit selection: verify manufacturer capacity at actual ambient, enclosure rating, altitude, installation clearance, and operating conditions.

About this calculator

Estimate active cooling needed to hold an enclosure at a target temperature. Inputs include internal equipment losses, other external heat gain, enclosure dimensions, ambient temperature, and an effective heat-transfer coefficient.

Method and assumptions

Six-sided area = 2 × (width × height + width × depth + height × depth). Passive heat transfer = effective coefficient × area × (ambient − target temperature). Required active cooling is the greater of zero and internal plus external heat plus passive ambient heat gain.

Dimensions convert from inches to meters; temperature difference converts from degrees Fahrenheit to kelvin. Cooling is reported in watts and BTU/h.

FAQs

How do I choose the heat-transfer coefficient?

Use a value supported by enclosure construction data or a manufacturer calculation. It depends on material, insulation, mounting, and surrounding airflow.

Can I select an air conditioner directly from this result?

No. The result is a steady-state heat-balance estimate. Select a unit using its rated performance at the actual ambient and installation conditions.

Sources

Use enclosure manufacturer thermal data and cooling unit capacity tables at the actual ambient and installation conditions.