AC power quality

Three-Phase Voltage Unbalance Calculator

Calculate a maximum-deviation voltage-unbalance percentage from three line-to-line RMS readings.

AC power quality

Enter measured or design values

V
V
V

Voltage unbalance

Maximum deviation from average
2.08 %
Average line voltage480 V
Maximum deviation10 V

This is the maximum-deviation method, not negative-sequence voltage unbalance.

Engineering review requiredPower-factor correction equipment requires harmonic, resonance, switching, protection, and manufacturer review. Unbalance results do not establish a universal pass/fail threshold.

About this calculator

Calculate a maximum-deviation voltage-unbalance percentage from three line-to-line RMS readings.

This maximum-deviation metric is not the negative-sequence voltage-unbalance method and does not apply a universal equipment limit.

Method and assumptions

Average voltage is the arithmetic mean of the three line-to-line readings. Percent unbalance is the largest absolute deviation from that average divided by the average, multiplied by 100.

Enter values measured or specified for the same load, system, and operating condition. These simplified calculations do not model harmonics, transient behavior, or equipment-specific acceptance limits.

FAQs

Does this result establish compliance or equipment acceptance?

No. It is a calculation or screening metric. Apply the equipment manufacturer criteria, project requirements, and locally applicable standards.

Which voltage readings should I enter?

For the voltage screen, enter all three RMS line-to-line readings measured at the same operating condition and point in the system.

Sources

Power triangle and maximum-deviation definitions as stated in the method above. Confirm manufacturer-specific criteria before applying results.