PV String and DC Wiring Calculator
Estimate cold-corrected PV string voltage, compare module ratings with one inverter MPPT input, and review DC homerun voltage drop.
PV module ratings
Use the negative coefficient shown on the module datasheet.
Use the negative coefficient shown on the module datasheet.
Selected MPPT input
Conductor voltage drop
Resistance reference only; this does not determine an approved PV conductor.
The calculator includes the positive and negative conductors and uses the combined current for this MPPT.
This is your design target, not a code limit.
Estimated Vmp range: 264.0–359.2 V. The check compares your entered module and inverter values only.
Smallest listed copper size meeting the entered voltage-drop target: 12 AWG
| Copper conductor | DC voltage drop | Percent drop | Target |
|---|---|---|---|
| 14 AWG | 11.29 V | 3.53% | Above target |
| 12 AWG | 7.13 V | 2.23% | Meets target |
| 10 AWG | 4.46 V | 1.40% | Meets target |
| 8 AWG | 2.80 V | 0.88% | Meets target |
| 6 AWG | 1.76 V | 0.55% | Meets target |
| 4 AWG | 1.11 V | 0.35% | Meets target |
| 3 AWG | 0.88 V | 0.28% | Meets target |
| 2 AWG | 0.70 V | 0.22% | Meets target |
| 1 AWG | 0.55 V | 0.17% | Meets target |
| 1/0 AWG | 0.44 V | 0.14% | Meets target |
| 2/0 AWG | 0.35 V | 0.11% | Meets target |
| 3/0 AWG | 0.27 V | 0.09% | Meets target |
| 4/0 AWG | 0.22 V | 0.07% | Meets target |
| 250 kcmil | 0.18 V | 0.06% | Meets target |
| 300 kcmil | 0.15 V | 0.05% | Meets target |
| 350 kcmil | 0.13 V | 0.04% | Meets target |
| 400 kcmil | 0.12 V | 0.04% | Meets target |
| 500 kcmil | 0.09 V | 0.03% | Meets target |
| 600 kcmil | 0.08 V | 0.02% | Meets target |
| 750 kcmil | 0.06 V | 0.02% | Meets target |
| 1000 kcmil | 0.05 V | 0.01% | Meets target |
About this calculator
Enter module datasheet values, the number of modules in series, and the number of parallel strings connected to one MPPT input. The calculator estimates cold-corrected string Voc, hot and cold Vmp, nameplate array current, and DC homerun voltage drop.
The inverter comparisons use the limits you enter from its documentation. A result within those limits is not an approval of the complete PV system.
Method and assumptions
Module voltages are treated as STC ratings at 25°C. The temperature-adjusted voltage is estimated with the module’s linear temperature coefficient. Cold-corrected Voc uses the lowest expected ambient temperature; Vmp uses the entered coldest and hottest cell temperatures.
Array Imp and Isc equal the module nameplate current multiplied by parallel strings on the selected MPPT. The DC voltage-drop estimate uses the combined Imp on a two-conductor homerun, Southwire DC resistance values at 25°C, and a linear copper resistance correction for conductor temperature.
The conductor comparison is voltage-drop-only. It does not check NEC 690 current factors, conductor ampacity, OCPD, equipment listing, wire type, disconnects, rapid shutdown, grounding, or all inverter limits. Replace every example input with the project module, inverter, climate, and installation data.
FAQs
Why does the calculator use the lowest ambient temperature for Voc?
A PV module’s open-circuit voltage rises as cell temperature falls. The cold-voltage estimate applies the entered module Voc temperature coefficient to the lowest expected ambient temperature. Verify the temperature method required by the adopted NEC edition and the equipment manufacturer.
Where do I find the module temperature coefficients?
Use the exact module datasheet. Enter a negative Voc and Vmp coefficient, in either percent per degree Celsius or volts per degree Celsius, matching the unit shown by the manufacturer.
What do the inverter current checks mean?
The tool compares nameplate Imp and Isc multiplied by the parallel strings assigned to the selected MPPT input with the inverter limits you enter. It does not apply NEC current factors or size source-circuit conductors or overcurrent devices.
Does the recommended conductor size mean the wire is code-compliant?
No. The comparison only finds a listed copper size that meets the entered voltage-drop target using the selected current, route length, and conductor temperature. Confirm ampacity, temperature correction, wiring method, PV conductor listing, overcurrent protection, terminals, and equipment instructions separately.
Sources
- NFPA 70 (NEC), 2026 edition, Article 690 — verify the adopted edition and all project-specific PV requirements.
- U.S. Department of Energy, Solar Photovoltaic Performance and Efficiency Basics — module voltage and output vary with operating temperature.
- Southwire SPEC 45201 and SPEC 10000 — copper-conductor DC resistance at 25°C.
- Southwire Power Cable Manual, 4th edition — copper resistance-temperature correction relationship.