Grounded system screening

Ground-Fault Loop Current Estimator

Estimate current from source voltage and the total resistance and reactance of a supported grounded fault loop.

Ground-fault loop model

Enter source and return-path impedance

V
Ω
Ω
Ω

Include the outgoing path and grounded return path through the fault point.

Ω
Impedance magnitude estimate

Ground-fault loop current

544.9 A
Total resistance0.17 Ω
Total reactance0.14 Ω
Loop impedance magnitude0.2202 Ω
Estimate onlyRequires complete source and fault-return impedance for the same operating configuration. This does not predict protective-device operation, touch voltage, shock risk, or code compliance. Ground-fault paths and system conditions require qualified review.

About this estimator

Enter source voltage to ground and the resistance and reactance for both the source and complete fault-loop path. The estimator reports a symmetrical current magnitude based on the entered series impedance.

Use source and conductor values for the actual system state and fault location.

Method and assumptions

Total resistance and reactance are the respective sums of source and loop values. Impedance magnitude = √(R² + X²). Estimated current = source voltage to ground ÷ impedance magnitude.

The model assumes a single series loop and does not calculate parallel return paths, arcing faults, protective-device time, or transient current.

FAQs

What belongs in fault-loop impedance?

Include source impedance and the complete outgoing and grounded return paths through the fault point. Use values that represent the same system configuration.

Does the result show that a breaker will trip?

No. Protective-device operation depends on its time-current characteristics and actual fault conditions. This calculator only estimates current from entered impedance.

Sources

Use a qualified short-circuit or grounding study and conductor/manufacturer data for the system and fault location being evaluated.