Equipment short-circuit rating

Equipment SCCR Comparison Calculator

Compare study-provided available fault current with the marked short-circuit current rating and voltage rating of an equipment assembly.

Equipment SCCR comparison

Enter study and nameplate values

kA
kA
V
V

SCCR comparison

Entered values pass this comparison
1.3 kA margin
Available fault current8.7 kA
Assembly SCCR10 kA
Voltage ratingAt or above system voltage
Comparison onlyUse available fault current from a qualified study and the marked SCCR for the complete listed assembly at the applicable voltage. Do not infer assembly SCCR from the lowest component rating or assume a series rating. This does not establish code compliance or protective-device coordination.

About this calculator

Enter the available fault current from a study, the assembly SCCR from the complete equipment nameplate, and the applicable system and equipment voltages. The result compares the entered values directly.

Method and assumptions

SCCR margin = entered assembly SCCR − entered available fault current. The tool also checks whether the entered equipment voltage rating is at least the entered system voltage.

All values are treated as valid, applicable, and from the same equipment configuration. The tool does not calculate fault current, evaluate series ratings, or verify the assembly listing.

FAQs

Where should available fault current come from?

Use the value from the current short-circuit study for the exact equipment location and system configuration.

Can I derive assembly SCCR from the smallest component rating?

No. Use the verified assembly marking or manufacturer documentation for the complete listed configuration.

Sources

Use the adopted electrical code requirements, the current study, and manufacturer/nameplate data for the complete assembly and system voltage.